MV Lead Sheathed

The core of our MV Lead Sheathed cables is provided by an impermeable and watertight lead alloy sheath to counter the corrosive effect of chemicals involved in these industries where the lead sheath thickness complies with IEC 60502-2. The lead sheathing’s resistance to sulfides, water, oil and corrosive chemicals found in the ground water, gives these cables an extended lifespan, making them a reliable option for large-scale, infrastructure-related uses.

At ARABIAN EXPERTS Cables, our range of Medium Voltage Lead Sheathed Cables comply with IEC 60502-2 requirements. In addition, the lead sheath is made of cable grade alloys in line with BS EN 12548.

Our cables come with a standard outer sheath made of extruded PVC/ST2 or PE/ST7 as per IEC 60502-2. Special requests can also be accommodated for the outer sheathing of our MV Lead Sheathed Cables. We are able to supply fire retardant PVC, anti-termite/anti-rodent PVC, sunlight resistant PVC, and oil resistant PVC.

Get Quote Now!

20160831_MV-sheathead-725
UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=3.5/6(7.2) kV

  • REQUEST A QUOTE

 

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm kg/km
10 25 5.9 220 2.5 12.1 1.2 1.6 22 1280
11 35 6.9 305 2.5 13.1 1.2 1.6 23 1440
12 50 8.1 414 2.5 14.3 1.3 1.7 25 1720
13 70 9.7 598 2.5 15.9 1.3 1.7 27 2030
14 95 11.4 827 2.5 17.6 1.4 1.8 29 2495
15 120 12.9 1043 2.5 19.1 1.4 1.8 31 2830
16 150 14.3 1287 2.5 20.5 1.5 1.9 32 3310
17 185 16.0 1610 2.5 22.2 1.5 1.9 34 3790
18 240 18.4 2116 2.6 24.8 1.6 2.0 37 4620
19 300 20.7 2650 2.8 27.7 1.6 2.1 41 5560
20 400 23.2 3384 3.0 30.6 1.7 2.2 45 6760
21 500 26.7 4352 3.2 34.5 1.8 2.3 49 8230
22 630 30.5 5623 3.2 38.3 1.9 2.5 54 10200
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km µF/Km KA KA A A V/A/km
25 0.727 0.444 0.760 0.26 3.575 1.457 160 170 0.842
35 0.524 0.426 0.745 0.29 5.005 1.543 195 200 0.632
50 0.387 0.408 0.720 0.32 7.150 1.793 230 235 0.488
70 0.268 0.388 0.694 0.37 10.010 1.924 285 295 0.362
95 0.193 0.378 0.679 0.39 13.585 2.273 340 360 0.283
120 0.153 0.364 0.660 0.44 17.160 2.424 385 420 0.239
150 0.124 0.354 0.645 0.48 21.450 2.759 430 475 0.208
185 0.0991 0.343 0.630 0.52 26.455 2.924 485 550 0.180
240 0.0754 0.332 0.611 0.56 34.320 3.488 560 650 0.154
300 0.0601 0.324 0.596 0.58 42.900 3.828 630 740 0.137
400 0.047 0.313 0.578 0.61 57.200 4.433 720 860 0.122
500 0.0366 0.306 0.564 0.64 71.500 5.211 800 990 0.111
630 0.0283 0.296 0.548 0.71 90.090 6.115 910 1140 0.1021

1. The code numbers to be read in conjuction with 02020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0202070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=6/10(12) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm kg/km
10 25 5.9 220 3.4 13.9 1.3 1.6 24 1500
11 35 6.9 305 3.4 14.9 1.3 1.7 26 1670
12 50 8.1 414 3.4 16.1 1.3 1.7 27 1870
13 70 9.7 598 3.4 17.7 1.4 1.8 29 2290
14 95 11.4 827 3.4 19.4 1.4 1.8 31 2660
15 120 12.9 1043 3.4 20.9 1.5 1.9 33 3120
16 150 14.3 1287 3.4 22.3 1.5 1.9 34 3500
17 185 16.0 1610 3.4 24.0 1.6 2.0 37 4100
18 240 18.4 2116 3.4 26.4 1.6 2.1 40 4900
19 300 20.7 2650 3.4 28.9 1.7 2.1 43 5840
20 400 23.2 3384 3.4 31.4 1.8 2.1 46 7000
21 500 26.7 4352 3.4 34.9 1.9 2.4 50 8450
22 630 30.5 5623 3.4 38.7 1.9 2.5 55 9600
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km  µF/Km KA KA A A V/A/km
25 0.727 0.460 0.770 0.21 3.575 1.755 160 170 0.846
35 0.524 0.440 0.751 0.23 5.005 1.849 195 200 0.635
50 0.387 0.420 726.000 0.25 7.150 1.961 230 235 0.490
70 0.268 0.401 0.700 0.29 10.010 2.283 285 295 0.364
95 0.193 0.383 0.691 0.31 13.585 2.454 340 360 0.284
120 0.153 0.376 0.666 0.34 17.160 2.802 385 420 0.242
150 0.124 0.364 0.650 0.37 21.450 2.953 430 475 0.210
185 0.0991 0.354 0.635 0.40 26.455 3.356 485 550 0.183
240 0.0754 0.341 0.615 0.45 34.320 3.678 560 650 0.156
300 0.0601 0.329 0.593 0.49 42.900 4.226 630 740 0.138
400 0.047 0.318 0.580 0.55 57.200 4.810 720 860 0.123
500 0.0366 0.308 0.565 0.60 71.500 5.569 800 990 0.111
630 0.0283 0.299 0.549 0.68 90.090 6.170 910 1140 0.103

1. The code numbers to be read in conjuction with 03020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0302070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=8.7/15(17.5) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm kg/km
10 25 5.9 220 4.5 16.1 1.3 1.7 27 1700
11 35 6.9 305 4.5 17.1 1.4 1.8 28 1950
12 50 8.1 414 4.5 18.3 1.4 1.8 30 2150
13 70 9.7 598 4.5 19.9 1.4 1.8 31 2450
14 95 11.4 827 4.5 21.6 1.5 1.9 34 2950
15 120 12.9 1043 4.5 23.1 1.5 2.0 35 3350
16 150 14.3 1287 4.5 24.5 1.6 20.0 37 3850
17 185 16.0 1610 4.5 26.2 1.6 2.1 40 4400
18 240 18.4 2116 4.5 28.6 1.7 2.2 42 5300
19 300 20.7 2650 4.5 31.1 1.7 2.2 45 6000
20 400 23.2 3384 4.5 33.6 1.8 2.3 48 7200
21 500 26.7 4352 4.5 37.1 1.9 2.4 52 8700
22 630 30.5 5623 4.5 40.9 2.0 2.6 57 10700
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km  µF/Km KA KA A A V/A/km
25 0.727 0.470 0.780 0.17 3.575 1.961 165 170 0.850
35 0.524 0.456 0.758 0.19 5.005 2.223 195 200 0.638
50 0.387 0.435 0.732 0.21 7.150 2.343 230 245 0.494
70 0.268 0.415 0.706 0.23 10.010 2.504 280 305 0.368
95 0.193 0.402 0.690 0.25 13.585 2.877 335 375 0.289
120 0.153 0.389 0.672 0.27 17.160 3.039 385 425 0.245
150 0.124 0.377 0.656 0.29 21.450 3.414 430 485 0.213
185 0.0991 0.366 0.641 0.32 26.455 3.655 490 560 0.185
240 0.0754 0.352 0.621 0.35 34.320 4.189 560 660 0.159
300 0.0601 0.340 0.605 0.39 42.900 4.495 640 750 0.141
400 0.047 0.327 0.585 0.43 57.200 5.095 720 870 0.125
500 0.0366 0.318 0.570 0.48 71.500 5.870 810 1000 0.114
630 0.0283 0.307 0.554 0.53 90.090 6.825 910 1150 0.105

1. The code numbers to be read in conjuction with 04020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0402070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=6/10(12) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm kg/km
10 25 5.9 670 3.4 13.9 1.8 2.4 50 5150
11 35 6.9 929 3.4 14.9 1.9 2.5 53 5900
12 50 8.1 1260 3.4 16.1 2.0 2.6 56 6800
13 70 9.7 1820 3.4 17.7 2.1 2.8 60 8150
14 95 11.4 2518 3.4 19.4 2.2 2.9 65 9650
15 120 12.9 3175 3.4 20.9 2.3 3.0 69 11150
16 150 14.3 3919 3.4 22.3 2.4 3.1 72 12650
17 185 16.0 4902 3.4 24.0 2.5 3.2 77 14600
18 240 18.4 6443 3.4 26.4 2.6 3.4 84 17650
19 300 20.7 8069 3.4 28.9 2.8 3.6 91 21050
Nominal Cross Section DC Resistance at 20°C Nominal Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(3) Voltage drop per phase
Conductor Screen per phase (2) Under- ground Cable Cable in Air
mm² ohm/km mH/km  µF/Km KA KA A A V/A/km
25 0.727 0.331 0.21 3.575 0.503 150 150 0.816
35 0.524 0.318 0.23 5.005 0.535 190 190 0.607
50 0.387 0.305 0.25 7.150 0.574 225 225 0.464
70 0.268 0.292 0.29 10.010 0.625 275 280 0.340
95 0.193 0.285 0.31 13.585 0.680 330 340 0.262
120 0.153 0.276 0.34 17.160 0.728 370 385 0.219
150 0.124 0.269 0.37 21.450 0.773 420 445 0.189
185 0.0991 0.263 0.40 26.455 0.827 470 510 0.162
240 0.0754 0.255 0.44 34.320 0.917 540 590 0.132
300 0.0601 0.248 0.48 42.900 0.997 580 620 0.120

1. The code numbers to be read in conjuction with 03020103 at the beginning and “L” at the end.

Example: for 150 mm² the code number is 0302010316L

Code number for different types of insulation screen : replace the 6th digit as follows:
2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

2. For Copper Tape screen only.

3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=6/10(12) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nom. Dia. of Alum. Wire Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm mm kg/km
10 25 5.9 220 3.4 13.9 1.3 1.6 1.8 30 1950
11 35 6.9 305 3.4 14.9 1.3 1.6 1.9 32 2100
12 50 8.1 414 3.4 16.1 1.3 1.6 1.9 33 2350
13 70 9.7 598 3.4 17.7 1.4 1.6 2.0 35 2750
14 95 11.4 827 3.4 19.4 1.4 2.0 2.0 38 3300
15 120 12.9 1043 3.4 20.9 1.5 2.0 2.1 40 3800
16 150 14.3 1287 3.4 22.3 1.5 2.0 2.1 41 4200
17 185 16.0 1610 3.4 24.0 1.6 2.0 2.2 44 4850
18 240 18.4 2116 3.4 26.4 1.6 2.0 2.3 47 5700
19 300 20.7 2650 3.4 28.9 1.7 2.5 2.4 51 6850
20 400 23.2 3384 3.4 31.4 1.8 2.5 2.5 54 8050
21 500 26.7 4352 3.4 34.9 1.9 2.5 2.6 59 9700
22 630 30.5 5623 3.4 38.7 1.9 2.5 2.7 63 11600
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km  µF/Km KA KA A A V/A/km
25 0.727 0.488 0.790 0.21 3.575 1.755 150 155 0.852
35 0.524 0.472 0.765 0.23 5.005 1.849 195 200 0.642
50 0.387 0.450 0.739 0.25 7.150 1.961 230 235 0.497
70 0.268 0.428 0.713 0.29 10.010 2.283 285 295 0.370
95 0.193 0.416 0.697 0.31 13.585 2.454 340 360 0.292
120 0.153 0.401 0.678 0.34 17.160 2.802 385 420 0.246
150 0.124 0.390 0.663 0.37 21.450 2.953 430 475 0.216
185 0.0991 0.378 0.647 0.40 26.455 3.356 485 550 0.188
240 0.0754 0.363 0.627 0.45 34.320 3.678 560 650 0.161
300 0.0601 0.351 0.611 0.49 42.900 4.226 630 740 0.143
400 0.047 0.338 0.591 0.55 57.200 4.810 720 860 0.128
500 0.0366 0.328 0.576 0.60 71.500 5.569 800 990 0.116
630 0.0283 0.317 0.560 0.68 90.090 6.170 910 1140 0.107

1. The code numbers to be read in conjuction with 03020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0302071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=8.7/15(17.5) kV

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nom. Dia. of Alum. Wire Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm mm kg/km
10 25 5.9 220 4.5 16.1 1.3 1.6 1.9 33 2150
11 35 6.9 305 4.5 17.1 1.4 1.6 1.9 34 2450
12 50 8.1 414 4.5 18.3 1.4 1.6 2.0 36 2700
13 70 9.7 598 4.5 19.9 1.4 2.0 2.1 39 3200
14 95 11.4 827 4.5 21.6 1.5 2.0 2.1 41 3700
15 120 12.9 1043 4.5 23.1 1.5 2.0 2.2 42 4100
16 150 14.3 1287 4.5 24.5 1.6 2.0 2.2 44 4600
17 185 16.0 1610 4.5 26.2 1.6 2.0 2.3 47 5200
18 240 18.4 2116 4.5 28.6 1.7 2.5 2.4 51 6350
19 300 20.7 2650 4.5 31.1 1.7 2.5 2.5 54 7200
20 400 23.2 3384 4.5 33.6 1.8 2.5 2.6 57 8450
21 500 26.7 4352 4.5 37.1 1.9 2.5 2.7 61 10100
22 630 30.5 5623 4.5 40.9 2.0 2.5 2.8 66 12200
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km µF/Km KA KA A A V/A/km
25 0.727 0.505 0.796 0.17 3.575 1.961 150 170 0.856
35 0.524 0.484 0.771 0.19 5.005 2.223 195 200 0.645
50 0.387 0.463 0.745 0.21 7.150 2.353 230 245 0.500
70 0.268 0.441 0.719 0.23 10.010 2.504 280 305 0.373
95 0.193 0.428 0.703 0.25 13.585 2.877 335 375 0.294
120 0.153 0.413 0.684 0.27 17.160 3.039 385 425 0.250
150 0.124 0.401 0.668 0.29 21.450 3.414 430 485 0.219
185 0.0991 0.388 0.652 0.32 26.455 3.655 490 560 0.190
240 0.0754 0.373 0.632 0.35 34.320 4.189 560 660 0.163
300 0.0601 0.361 0.616 0.39 42.900 4.495 640 750 0.146
400 0.047 0.346 0.596 0.43 57.200 5.095 720 870 0.130
500 0.0366 0.337 0.582 0.48 71.500 5.870 810 1000 0.118
630 0.0283 0.325 0.565 0.53 90.090 6.825 910 1150 0.109

1. The code numbers to be read in conjuction with 04020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0402071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2 

Uo/U (Um)=12/20(24) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm kg/km
10 25 5.9 220 6.0 19.1 1.4 1.8 31 2050
11 35 6.9 305 5.5 19.1 1.4 1.8 31 2150
12 50 8.1 414 5.5 20.3 1.5 1.9 32 2450
13 70 9.7 598 5.5 21.9 1.5 1.9 34 2800
14 95 11.4 827 5.5 23.6 1.6 2.0 36 3300
15 120 12.9 1043 5.5 25.1 1.6 2.0 38 3700
16 150 14.3 1287 5.5 26.5 1.6 2.1 40 4150
17 185 16.0 1610 5.5 28.2 1.7 2.1 42 4700
18 240 18.4 2116 5.5 30.6 1.7 2.2 45 5450
19 300 20.7 2650 5.5 33.1 1.8 2.3 48 6450
20 400 23.2 3384 5.5 35.6 1.9 2.4 51 7600
21 500 26.7 4352 5.5 39.1 2.0 2.5 55 9300
22 630 30.5 5623 5.5 42.9 2.1 2.6 60 11150
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km µF/Km KA KA A A V/A/km
25 0.727 0.497 0.792 0.14 3.575 2.424 165 170 0.854
35 0.524 0.468 0.763 0.16 5.005 2.424 195 200 0.641
50 0.387 0.448 0.738 0.18 7.150 2.737 230 145 0.497
70 0.268 0.426 0.712 0.20 10.010 2.910 280 305 0.370
95 0.193 0.414 0.696 0.21 13.585 3.310 335 375 0.291
120 0.153 0.399 0.677 0.23 17.160 3.483 385 425 0.247
150 0.124 0.388 0.662 0.25 21.450 3.690 430 485 0.216
185 0.0991 0.375 0.646 0.27 26.455 4.140 490 560 0.187
240 0.0754 0.361 0.626 0.30 34.320 4.433 560 660 0.161
300 0.0601 0.350 0.610 0.33 42.900 5.031 640 750 0.143
400 0.047 0.336 0.590 0.37 57.200 5.665 720 870 0.127
500 0.0366 0.326 0.575 0.40 71.500 6.567 810 1000 0.115
630 0.0283 0.315 0.558 0.45 90.090 7.483 910 1150 1.070

1. The code numbers to be read in conjuction with 05020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0502070116. 

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV

UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=18/30(36) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm kg/km
12 50 8.1 414 8.0 25.3 1.6 2.1 38 3100
13 70 9.7 598 8.0 26.9 1.7 2.1 40 3650
14 95 11.4 827 8.0 28.6 1.7 2.2 42 4100
15 120 12.9 1043 8.0 30.1 1.7 2.2 44 4450
16 150 14.3 1287 8.0 31.5 1.8 2.3 46 5000
17 185 16.0 1610 8.0 33.2 1.8 2.3 48 5500
18 240 18.4 2116 8.0 35.6 1.9 2.4 51 6450
19 300 20.7 2650 8.0 38.1 2.0 2.5 54 7500
20 400 23.2 3384 8.0 40.6 2.0 2.6 57 8700
21 500 26.7 4352 8.0 44.1 2.1 2.7 61 10250
22 630 30.5 5623 0.0 47.9 2.2 2.8 66 12250
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km µF/Km KA KA A A V/A/km
50 0.387 0.482 0.755 0.14 7.150 3.506 230 245 0.504
70 0.268 0.459 0.728 0.16 10.010 3.982 280 305 0.377
95 0.193 0.446 0.712 0.17 13.585 4.189 335 375 0.299
120 0.153 0.430 0.693 0.18 17.160 4.372 385 425 0.254
150 0.124 0.417 0.677 0.19 21.450 4.824 430 485 0.222
185 0.0991 0.404 0.661 0.21 26.455 5.043 490 560 0.194
240 0.0754 0.388 0.641 0.23 34.320 5.665 560 660 0.167
300 0.0601 0.375 0.624 0.25 42.900 6.337 640 750 0.149
400 0.047 0.360 0.604 0.27 57.200 6.782 720 870 0.133
500 0.0366 0.349 0.589 0.30 71.500 7.664 810 1000 0.121
630 0.0283 0.338 0.570 0.33 90.090 8.646 910 1150 0.1121.

1. The code numbers to be read in conjuction with 06020701 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows:
7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0602070116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV

  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE

    COPPER CONDUCTORS

    STANDARD : IEC 60502-2

    Uo/U (Um)=3.5/6(7.2) kV

    • REQUEST A QUOTE

     

    Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
      mm² mm kg/km mm mm mm mm mm kg/km
    10 25 5.9 670 2.5 12.1 1.6 2.2 45 4300
    11 35 6.9 929 2.5 13.1 1.7 2.3 48 4900
    12 50 8.1 1260 2.5 14.3 1.8 2.4 51 5800
    13 70 9.7 1820 2.5 15.9 1.9 2.5 55 7000
    14 95 11.4 2518 2.5 17.6 2.0 2.6 60 8400
    15 120 12.9 3175 2.5 19.1 2.1 2.7 64 9700
    16 150 14.3 3919 2.5 20.5 2.1 2.8 67 10950
    17 185 16.0 4902 2.5 22.2 2.2 3.0 72 12750
    18 240 18.4 6443 2.6 24.8 2.4 3.2 79 15750
    19 300 20.7 8069 2.8 27.7 2.6 3.3 87 19250
    Nominal Cross Section DC Resistance at 20°C Nominal Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(3) Voltage drop per phase
    Conductor Screen per phase (2) Under- ground Cable Cable in Air
    mm² ohm/km mH/km µF/Km KA KA A A V/A/km
    25 0.727 0.305 0.26 3.575 0.446 150 150 0.811
    35 0.524 0.294 0.29 5.005 0.478 190 190 0.602
    50 0.387 0.283 0.32 7.150 0.516 225 225 0.459
    70 0.268 0.272 0.36 10.010 0.568 275 280 0.335
    95 0.193 0.266 0.39 13.585 0.622 330 340 0.258
    120 0.153 0.259 0.43 17.160 0.670 370 385 0.215
    150 0.124 0.253 0.47 21.450 0.715 420 445 0.185
    185 0.0991 0.250 0.52 26.455 0.770 470 510 0.159
    240 0.0754 0.243 0.56 34.320 0.853 540 590 0.134
    300 0.0601 0.236 0.58 42.900 0.959 580 620 0.1171.

    1. The code numbers to be read in conjuction with 02020103 at the beginning and “L” at the end.

    Example: for 150 mm² the code number is 0202010316L

    Code number for different types of insulation screen : replace the 6th digit as follows: 2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

    2. For Copper Tape screen only.

    3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

    For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=12/20(24) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nom. Dia. of Alum. Wire Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm mm kg/km
10 25 5.9 220 6.0 19.1 1.4 2.0 2.0 38 2750
11 35 6.9 305 5.5 19.1 1.4 2.0 2.0 38 2800
12 50 8.1 414 5.5 20.3 1.5 2.0 2.1 39 3150
13 70 9.7 598 5.5 21.9 1.5 2.0 2.1 41 3550
14 95 11.4 827 5.5 23.6 1.6 2.0 2.2 43 4100
15 120 12.9 1043 5.5 25.1 1.6 2.0 2.3 45 4500
16 150 14.3 1287 5.5 26.5 1.6 2.0 2.3 47 5000
17 185 16.0 1610 5.5 28.2 1.7 2.5 2.4 50 5850
18 240 18.4 2116 5.5 30.6 1.7 2.5 2.5 53 6650
19 300 20.7 2650 5.5 33.1 1.8 2.5 2.6 56 7650
20 400 23.2 3384 5.5 35.6 1.9 2.5 2.7 59 8950
21 500 26.7 4352 5.5 39.4 2.0 2.5 2.8 64 10750
22 630 30.5 5623 5.5 42.9 2.1 2.5 2.9 69 12800
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km µF/Km KA KA A A V/A/km
25 0.727 0.524 0.805 0.14 3.575 2.424 165 170 0.860
35 0.524 0.496 0.776 0.16 5.005 2.424 195 200 0.647
50 0.387 0.474 0.751 0.18 7.150 2.737 230 245 0.502
70 0.268 0.452 0.724 0.20 10.010 2.910 280 305 0.376
95 0.193 0.438 0.708 0.21 13.585 3.310 335 375 0.299
120 0.153 0.432 0.689 0.23 17.160 3.483 385 425 0.253
150 0.124 0.410 0.673 0.25 21.450 3.690 430 485 0.221
185 0.0991 0.397 0.657 0.27 26.455 4.140 490 560 0.192
240 0.0754 0.382 0.637 0.30 34.320 4.433 560 660 0.165
300 0.0601 0.370 0.621 0.33 42.900 5.031 640 750 0.148
400 0.047 0.355 0.601 0.37 57.200 5.665 720 870 0.132
500 0.0366 0.345 0.586 0.40 71.500 6.567 810 1000 0.120
630 0.0283 0.333 0.569 0.45 90.090 6.567 910 1150 0.111

1. The code numbers to be read in conjuction with 05020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0502071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV

ARMOURED SINGLE CORE LEAD SHEATHED CABLE

COPPER CONDUCTORS

STANDARD : IEC 60502-2

Uo/U (Um)=18/30(36) kV

  • REQUEST A QUOTE

 

Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Nom. Dia. of Alum. Wire Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
  mm² mm kg/km mm mm mm mm mm mm kg/km
12 50 8.1 414 8.0 25.3 1.6 2.0 2.3 45 3900
13 70 9.7 598 8.0 26.9 1.7 2.0 2.3 48 4500
14 95 11.4 827 8.0 28.6 1.7 2.5 2.4 51 5150
15 120 12.9 1043 8.0 30.1 1.7 2.5 2.5 53 5600
16 150 14.3 1287 8.0 31.5 1.8 2.5 2.5 54 6150
17 185 16.0 1610 8.0 33.2 1.8 2.5 2.6 56 6750
18 240 18.4 2116 8.0 35.6 1.9 2.5 2.7 59 7800
19 300 20.7 2650 8.0 38.1 2.0 2.5 2.8 63 8900
20 400 23.2 3384 8.0 40.6 2.0 2.5 2.9 66 10200
21 500 26.7 4352 8.0 44.1 2.1 2.5 3.0 70 11900
22 630 30.5 5623 8.0 47.9 2.2 2.5 3.1 75 13950
Nominal Cross Section DC Resistance at 20°C Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(2) Voltage drop per phase
Trefoil Flat Conductor Screen Under- ground Cable Cable in Air
mm² ohm/km mH/km mH/km µF/Km KA KA A A V/A/km
50 0.387 0.504 0.766 0.14 7.150 3.506 230 245 0.509
70 0.268 0.481 0.740 0.16 10.010 3.982 280 305 0.382
95 0.193 0.467 0.723 0.17 13.585 4.189 335 375 0.303
120 0.153 0.450 0.704 0.18 17.160 4.372 385 425 0.259
150 0.124 0.437 0.688 0.19 21.450 4.824 430 485 0.227
185 0.0991 0.424 0.672 0.21 26.455 5.043 490 560 0.198
240 0.0754 0.407 0.652 0.23 34.320 5.665 560 660 0.171
300 0.0601 0.394 0.635 0.25 42.900 6.337 640 750 0.153
400 0.047 0.377 0.614 0.27 57.200 6.782 720 870 0.137
500 0.0366 0.366 0.599 0.30 71.500 7.664 810 1000 0.125
630 0.0283 0.357 0.582 0.33 90.090 8.646 910 1150 0.115

1. The code numbers to be read in conjuction with 06020711 at the beginning.

Code number for different types of insulation screen : replace the 6th digit as follows: 7 for STRIPPABLE + LEAD; 8 for BONDED + LEAD; 9 for GRAPHITE + LEAD

Example: for 150 mm² Strippable + Lead cable, the code number is 0602071116.

2. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.

ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV

  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • UN-ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • UN-ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(33) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • ARMOURED SINGLE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=3.5/6(7.2) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=6/10(12) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=8.7/15(17.5) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=12/20(24) kV


  • ARMOURED THREE CORE LEAD SHEATHED CABLE Uo/U (Um)=18/30(36) kV

    ARMOURED THREE CORE LEAD SHEATHED CABLE

    COPPER CONDUCTORS

    STANDARD : IEC 60502-2

    Uo/U (Um)=18/30(36) kV

    • REQUEST A QUOTE

     

    Code Number (1) Nominal Cross Section Nominal Dia. of Cond. Weight of Cond. Nominal Insulation Thick. Approx. diameter over insulation Nominal Lead Sheath Thick. Armour Steel Wire Dia. Nominal PVC Sheath Thick. Approx. External Diameter Approx. Weight of Cable
      mm² mm kg/km mm mm mm mm mm mm kg/km
    12 50 8.1 1260 8.0 25.3 2.5 3.15 3.6 92 17300
    13 70 9.7 1820 8.0 26.9 2.6 3.15 3.8 98 19450
    14 95 11.4 2518 8.0 28.6 2.7 3.15 3.9 102 21500
    15 120 12.9 3175 8.0 30.1 2.8 3.15 4.0 106 23400
    16 150 14.3 3919 8.0 31.5 2.9 3.15 4.1 110 25300
    17 185 16.0 4902 8.0 33.2 3.0 3.15 4.2 114 27750
    18 240 18.4 6443 8.0 35.6 3.1 3.15 4.4 120 31150
    19 300 20.7 8069 8.0 38.1 3.2 3.15 4.6 127 35050
    Nominal Cross Section DC Resistance at 20°C Nominal Inductance Capacitance Short circuit current for 1 sec. Current Carrying Capacity(3) Voltage drop per phase
    Conductor Screen per phase (2) Under- ground Cable Cable in Air
    mm² ohm/km mH/km  µF/Km KA KA A A V/A/km
    50 0.387 0.449 0.14 7.150 0.869 225 230 0.497
    70 0.268 0.430 0.16 10.010 0.933 270 280 0.372
    95 0.193 0.419 0.17 13.585 0.988 330 345 0.292
    120 0.153 0.405 0.18 17.160 1.036 370 395 0.248
    150 0.124 0.395 0.19 21.450 1.081 415 450 0.217
    185 0.0991 0.384 0.21 26.455 1.135 465 510 0.189
    240 0.0754 0.371 0.23 34.320 1.212 540 600 0.163
    300 0.0601 0.358 0.25 42.900 1.292 610 680 0.143

    1. The code numbers to be read in conjuction with 06020123 at the beginning and “L” at the end.

    Example: for 150 mm² the code number is 0602012316L

    Code number for different types of insulation screen : replace the 6th digit as follows: 2 for S + CUW; 3 for B + CUT; 4 for B + CUW; 5 for G + CUT and 6 for G + CUW

    2. For Copper Tape screen only.

    3. Laying Conditions : Underground temperature of soil 20°C, Ground Thermal resistivity 100°C cm/W, ambient temperature 30°C.

    For other laying conditions, please refer to Table nos. 1 – 5 for derating factors.